Ac and dc grounding requirements – Outback Power Systems GVFX Series Inverter/Charger Installation Manual User Manual
Page 54
52
AC AND DC GROUNDING REQUIREMENTS
• Connect only to a grounded, permanent wiring system. Ensure there is only one neutral-ground
connection in the system at any time. Some codes require this connection be made at the main
panel only.
• Some generators have their own neutral-ground connection. If a generator is used, its neutral-
ground connection will need to be disengaged for proper system operation.
• For all installations, the negative battery conductor should be bonded to the grounding system at
one (and only one) point in the system.
• OutBack products are not designed for use in a positive grounded system. Please contact OutBack
Technical Support for further information.
the equipment ground on each is marked with this symbol:
Box lug for grounding the FX chassis