Wire sizes, Awg wire sizes – Outback Power Systems GVFX Series Inverter/Charger Installation Manual User Manual
Page 82
80
(with insulation)
WIRE SIZES
The following chart contains information on wire sizes, the DC resistance of the wires and the
corresponding diameters and areas of these wires. This information can be used to calculate the
voltage drop of the wires or to find an equivalent wire size.
SIZE
DC
CROSS-SECTIONAL AREA
APPROXIMATE DIAMETER
(AWG)
Resistance in Ohms
(1000 feet)
INCHES
MILLIMETERS
INCHES
MILLIMETERS
14
3.14
0.0032
2.08
.078
1.98
12
1.98
0.0051
3.31
.101
2.57
10
1.24
0.0082
5.26
.126
3.20
8
0.78
0.0130
8.37
.162
4.11
6
0.50
0.0206
13.30
.215
5.46
4
0.31
0.0328
21.15
.269
6.83
2
0.19
0.0521
33.62
.337
8.56
1
0.15
0.0657
42.41
.376
9.55
1/0
0.12
0.0829
53.50
.423
10.74
2/0
0.10
0.1045
67.43
.508
12.90
3/0
0.08
0.1318
85.01
.576
14.63
4/0
0.06
0.1662
107.20
.645
16.38
Size #14 #12 #10 #8 #6 #4 #3 #2 #1 1/0
Diameter 0.073 0.080 0.115 0.146 0.184 0.235 0.281 0.295 0.335 0.380
(inches)
Size 2/0 3/0 4/0 250 MCM 300 MCM 350 MCM 400 MCM 500 MCM
Diameter 0.420 0.475 0.530 0.580 0.635 0.690 0.730 0.820
(inches)
AWG Wire Sizes
Note: These sizes represent the conductor only without any insulation.
Note: These illustrations may not be to scale and are for example purposes only.