SERIES DUAL FX CONFIGURATION

• This system can continuously power between 4.0 kW and 7.2 kW of 120/240 VAC loads, depending

on which model is used.

• Connecting more power than the continuous rating of the FX may cause breakers to trip or the FX to shut off

its AC output.

• All FX AC wiring must be sized to handle 60 amps AC or more.

Note:
• Stacking FXs in series means there are FXs directly connected to two legs of a 120/240 VAC input

source, and to two separate 120 VAC output legs.

• In the event of grid failure, each 120 VAC leg can provide the full wattage of that inverter to the loads

on that circuit.

• These series-stacked 120 VAC legs produce 240 VAC between them. In the event of grid failure, they

can provide the full wattage of both inverters to any 240 VAC loads.

• The Slave FX must be programmed through the MATE as a “Classic Slave’” . The FX connected to Port

01 of the HUB is always the Master (1-2ph MASTER).

• Other options must not be selected, with the exception of three-phase operation, which will be

described next.

• Stacked Grid-Tie FXs should not be used with the FW-X240 Auto Transformer.