Maximum overcurrent protection – Outback Power Systems GVFX Series Inverter/Charger Installation Manual User Manual
Page 80
78
MODEL
AMPACITY
DC BREAKER
DC FUSE
GTFX2524LA
125 A
OBDC-175
Class T-300
GTFX3048LA
75 A
OBDC-100
Not Recommended
GVFX3524LA
175 A
OBDC-250
Class T-400
GVFX3648LA
90 A
OBDC-125
Not Recommended
MAXIMUM CONTINUOUS OUTPUT POWER
An FX Series Inverter/Charger’s model number indicates its maximum continuous output power by
changing the last two digits to zeros. For instance, a GTFX2524LA has a maximum continuous output
power of 2500VA (volt-amps).
GTFX2524LA
2500 VA (VA = volt-Amps)
GTFX3048LA
3000 VA
GVFX3524LA
3500 VA
GVFX3648LA
3600 VA
MAXIMUM OVERCURRENT PROTECTION
This rating specifies the proper overcurrent protection size.
• OBB breakers are panel-mount circuit breakers.
• Class T DC fuses are terminal-mounted and should always be used in conjuncture with a disconnect mechanism.
• FXs used in home installations should use properly sized DC circuit breakers.
• A DC breaker includes both overcurrent protection and disconnect capability.