Maximum overcurrent protection – Outback Power Systems GVFX Series Inverter/Charger Installation Manual User Manual

Page 80

background image

78

MODEL

AMPACITY

DC BREAKER

DC FUSE

GTFX2524LA

125 A

OBDC-175

Class T-300

GTFX3048LA

75 A

OBDC-100

Not Recommended

GVFX3524LA

175 A

OBDC-250

Class T-400

GVFX3648LA

90 A

OBDC-125

Not Recommended

MAXIMUM CONTINUOUS OUTPUT POWER

An FX Series Inverter/Charger’s model number indicates its maximum continuous output power by
changing the last two digits to zeros. For instance, a GTFX2524LA has a maximum continuous output
power of 2500VA (volt-amps).

GTFX2524LA

2500 VA (VA = volt-Amps)

GTFX3048LA

3000 VA

GVFX3524LA

3500 VA

GVFX3648LA

3600 VA

MAXIMUM OVERCURRENT PROTECTION

This rating specifies the proper overcurrent protection size.

• OBB breakers are panel-mount circuit breakers.
• Class T DC fuses are terminal-mounted and should always be used in conjuncture with a disconnect mechanism.
• FXs used in home installations should use properly sized DC circuit breakers.
• A DC breaker includes both overcurrent protection and disconnect capability.