3-PHASE FX SYSTEM

• This system produces 120 VAC per phase and 208 VAC from phase to phase. There can only be one FX per

phase on a 3-phase system.

• All FX AC wiring must be sized to handle 60 amps AC or more.
• This system can power continuously up to 10.8 kW of loads depending on which model is used.
• Connecting more power than the continuous rating of the FX may cause breakers to trip or the FX to shut off its

AC output.

• The jumper in the HUB must be left in the standard position (usually called the “series/parallel” position) for

3-phase configuration with LA Series grid-tied models. (This instruction is specific for these models, and may
conflict with the HUB Installation and User Guide).

Note:

Program the bottom FX as Master and the two upper FXs as 3-phase Slaves (3p Classic

B and 3p Classic C). Keep the phases in order: phase one is connected to the FX programmed
Master; phase two is connected to 3p Classic B; and phase three to 3p Classic C).