• Use crimped and sealed copper ring terminal lugs with 5/16” (0.79 cm) hole or compression-type
lug to connect battery cables to DC terminals. Soldered cable lugs are also acceptable.
• Use recommended cable sizes (see page 36) to reduce losses and ensure high performance of FX
(smaller cables can reduce performance and possibly damage the unit).
• Keep cables together (e.g., using a tie-wrap) as much as possible.
• Ensure cables pass through the same knockout and conduit fittings to allow inductive currents to
cancel.
TORQUE REQUIREMENTS
CONNECTION
TORQUE INCH-POUNDS/Nm
AC and PV breakers
to 22 inch-lbs/2.48 Nm
DC shunt
to 15 foot-lbs/20.4 Nm
DC battery connections
to 10 foot-lbs/13.6 Nm
FX’s DC terminals
to 5 foot-lbs/3.38 Nm
FX’s AC terminals
to 30 inch-lbs/3.38 Nm
Table 1 Torque Values for Installation