AC WIRING NOTES
AC HOT OUT
• AC hot output conductor (black) wire
gauge must be sized to the breakers and
loads
.
AC NEUTRAL OUT/AC NEUTRAL IN
• Both neutral terminals are common with
each other within the FX.
• Only one neutral needs to connect at the
terminal if a separate common neutral bus
bar is installed.
CHASSIS GROUND
• Both CHASSIS GROUND terminals are
common within the FX.
• The AC input and AC output ground
wires can connect to these terminals, or
one ground wire can be connected if a
common ground bus bar is installed.
AC HOT IN
• The AC hot input conductor (black) must
be supplied through a 60 amp maximum
AC branch rated circuit breaker.
• 6 AWG (0.184” or 4.11 mm) wire is
recommended for the FX’s AC transfer
relay.
����������
��������������
�����������������
�����������������
�������������
���������
�
�
��
��
�
��
��
�
�
��
�
��
�
��
�
��
�
��
��
�
�
�
��
�
��
�
�
�
������������
��������
��
�
��
��
�
��
�
��
��
��
�
��
��
�
�
�
��
��
�
�
�
�
�
�
�
�
�
�
��
�
�
��