AC WIRING NOTES

AC HOT OUT

• AC hot output conductor (black) wire

gauge must be sized to the breakers and
loads

.

AC NEUTRAL OUT/AC NEUTRAL IN

• Both neutral terminals are common with

each other within the FX.

• Only one neutral needs to connect at the

terminal if a separate common neutral bus
bar is installed.

CHASSIS GROUND

• Both CHASSIS GROUND terminals are

common within the FX.

• The AC input and AC output ground

wires can connect to these terminals, or
one ground wire can be connected if a
common ground bus bar is installed.

AC HOT IN

• The AC hot input conductor (black) must

be supplied through a 60 amp maximum
AC branch rated circuit breaker.

• 6 AWG (0.184” or 4.11 mm) wire is

recommended for the FX’s AC transfer
relay.

����������

��������������

�����������������

�����������������

�������������

���������

��

��

��

��

��

��

��

��

��

��

��

��

������������

��������

��

��

��

��

��

��

��

��

��

��

��

��

��