beautypg.com

Problem probable cause solution – AirSep MN138-1 H User Manual

Page 35

background image

29

MN138-1 Rev H

02/14

Problem

Probable Cause

Solution


Compressor relief valve activates
(popping sound)

Faulty electrical connection at waste
valve.

Faulty solenoid valve coil.

(Acceptable rating: 713-837 Ohms)

Contaminated sieve beds.

Faulty circuit board.

Faulty relief valve.

Repair electrical connection.

Replace valve coil. (Use of an
ohmmeter can be helpful to easily
determine faulty coil).

Replace sieve beds.

Replace circuit board.

Replace relief valve.

Unit alarms with

l/0

power switch

in “

I

” position. Circuit breaker

repeatedly trips.

Faulty electrical connection.

Faulty capacitor.

Faulty circuit breaker.

Faulty compressor.

Faulty circuit board.

Repair electrical connection.

Replace capacitor.

Replace circuit breaker.

Replace compressor.

Replace circuit board.

Cabinet fan does not turn.

Faulty electrical connections.

Faulty cabinet fan.

Check electrical connections.

Replace cabinet fan.

Flowmeter fluctuates

Improperly set or faulty product
regulator.

Leak.

Reduced air intake (suction)

Faulty flowmeter.

Worn compressor.

Faulty circuit board.

Faulty solenoid valve.

Check regulator setting. Repair or
replace regulator.

Leak test and repair leak.

Check compressor intake path for
obstruction. Remove obstruction.

Replace flowmeter.

Replace compressor

Replace circuit board.

Replace solenoid valve manifold.

Limited or low flow.

Restriction in humidifier/tubing.

Product regulator set too low.

Leak.

Reduced air intake (suction)


Weak compressor

Faulty circuit board

Restriction in mixing tank

Faulty solenoid valve.

Replace humidifier or tubing.

Adjust regulator setting.

Leak test and repair.

Check compressor intake path for
obstruction and remove, if needed.

Check system pressure, and rebuild or
exchange compressor.

Replace circuit board.

Replace mixing tank

Replace valve manifold.




No flow indicated on flow meter,
and 6-beep no flow alarm does
not activate.

Internal leak. (likely in location from
unit regulator to flow meter)



Main circuit boards prior to Rev. R do
not have a ‘no flow’ alarm

Leak test and repair. In particular,
regulator / fittings following air path
to flow meter. Repair leaks.