Problem probable cause solution – AirSep MN138-1 H User Manual
Page 35

29
MN138-1 Rev H
02/14
Problem
Probable Cause
Solution
Compressor relief valve activates
(popping sound)
•
Faulty electrical connection at waste
valve.
•
Faulty solenoid valve coil.
•
(Acceptable rating: 713-837 Ohms)
•
Contaminated sieve beds.
•
Faulty circuit board.
•
Faulty relief valve.
•
Repair electrical connection.
•
Replace valve coil. (Use of an
ohmmeter can be helpful to easily
determine faulty coil).
•
Replace sieve beds.
•
Replace circuit board.
•
Replace relief valve.
Unit alarms with
l/0
power switch
in “
I
” position. Circuit breaker
repeatedly trips.
•
Faulty electrical connection.
•
Faulty capacitor.
•
Faulty circuit breaker.
•
Faulty compressor.
•
Faulty circuit board.
•
Repair electrical connection.
•
Replace capacitor.
•
Replace circuit breaker.
•
Replace compressor.
•
Replace circuit board.
Cabinet fan does not turn.
•
Faulty electrical connections.
•
Faulty cabinet fan.
•
Check electrical connections.
•
Replace cabinet fan.
Flowmeter fluctuates
•
Improperly set or faulty product
regulator.
•
Leak.
•
Reduced air intake (suction)
•
Faulty flowmeter.
•
Worn compressor.
•
Faulty circuit board.
•
Faulty solenoid valve.
•
Check regulator setting. Repair or
replace regulator.
•
Leak test and repair leak.
•
Check compressor intake path for
obstruction. Remove obstruction.
•
Replace flowmeter.
•
Replace compressor
•
Replace circuit board.
•
Replace solenoid valve manifold.
Limited or low flow.
•
Restriction in humidifier/tubing.
•
Product regulator set too low.
•
Leak.
•
Reduced air intake (suction)
•
Weak compressor
•
Faulty circuit board
•
Restriction in mixing tank
•
Faulty solenoid valve.
•
Replace humidifier or tubing.
•
Adjust regulator setting.
•
Leak test and repair.
•
Check compressor intake path for
obstruction and remove, if needed.
•
Check system pressure, and rebuild or
exchange compressor.
•
Replace circuit board.
•
Replace mixing tank
•
Replace valve manifold.
No flow indicated on flow meter,
and 6-beep no flow alarm does
not activate.
•
Internal leak. (likely in location from
unit regulator to flow meter)
•
Main circuit boards prior to Rev. R do
not have a ‘no flow’ alarm
•
Leak test and repair. In particular,
regulator / fittings following air path
to flow meter. Repair leaks.