7
Operation
7.1 Minimum load requirements for the XB3 with voltage outputs
The following requirements apply to any external device or circuit connected to the XB3 transmitter with
voltage outputs:
In the situation where the external device uses an internal pull-up resistor the value of this resistor should
meet the requirements shown below. It is also necessary to add a pull-down resistor RL connected to ground
in order to be able to read 100% of the range of the XB3 voltage output.
7.2 XB2 and XB3 transmitters (analog outputs)
If so desired, use the HW4 software to configure the XB transmitter. Complete the mechanical and electrical
installation and simply power up the transmitter.
XB3 output signal
Input resistance RL
0…1V >=1kOhm
0…5V >=5kOhm
0…10V >=10kOhm
XB3 signal
VCC
R pull-up
RL
0…1V 3.3V
≥ 250 kOhm
1 kOhm
XB3 signal
VCC
R pull-up
RL
0…1V 5.0V
≥ 400 kOhm
1 kOhm
0…5V 5.0V
≥ 400 kOhm
5 kOhm
XB3 signal
VCC
R pull-up
RL
0…1V 10.0V
≥ 1 MOhm
1 kOhm
0…5V 10.0V
≥ 1 MOhm
5 kOhm
0…10V 10.0V
≥ 1 MOhm
10 kOhm
RL
GND
XB3
Voltage Output
R Pull-up
RL
GND
VCC
XB3
Voltage Output