direct current from 60 V to 400 V
(unshielded)
alternate current from 25V to 400 V
(unshielded)
in separated bundles or channels /
conduits, without minimum distance
direct and alternate current > 400 V
(unshielded)
Telephone lines
lines leading into EX-rated areas
in separated bundles or channels /
conduits, without minimum distance
Lightning protection
Cabling in areas with a risk of lightning requires a lightning protection. For cabling underground in between
buildings, we recommend the use of special fiber optic cables. If this is not possible, use copper cables that
are suitable for underground installation.
6.2 Wiring and terminal block diagrams
6.2.1
XB2: 2-wire, loop powered transmitter
Electrical diagram
The maximum permissible cable length connecting
the XB2 to other devices is determined by the total
resistance resulting from the addition of the cable
resistance and that of the devices connected in series
with the unit. This resistance should not exceed 500
ohms.