6.4.4
Scaling of the Analog Input
The analog input can be scaled within the range 0…3.2 V / 0…25 mA. If, for example, only 1...2.5 V are to be
shown in the display due to the application or a connected third-party probe, the analog input must be scaled
accordingly. Figure 16 illustrates scaling of the analog input.
Legend for
Figure 16
:
Input-Range:
0…3.2 V / 0…25 mA
RangeLo:
0 V / 0 mA (lowest input value)
RangeHi:
3.2 V / 25 mA (highest input value)
ScaleLo:
Bottom scale limit (min. value shown in display)
ScaleHi:
Top scale limit (max. value shown in display)
Figure 16: Graphic representation of scaling the analog input
Example:
An ambient pressure sensor with an analog output of 500…1000 mV (900…1100 hPa) is to be connected and
its signal shown in hPa. The
Input-Range
with the limits
RangeLo
= 500 mV and
RangeHi
= 1000 mV and the
display range Scale with
ScaleLo
= 900 and
ScaleHi
= 1100 mean that an input voltage of 500 mV shows the
value 900 in the display and an input voltage of 1000 mV the value 1100. The unit is configured with the HW4
software as "hPa".
Remark on PF4 with HC2 and analog input:
The formula for calculation of the
Display-Value
is:
∗