beautypg.com

Dwyer 32A User Manual

Page 35

background image

Page 35

Input Ranges (Field Selectable)

Thermocouple Types

Input
Type
Range
1° F
1°C
Input
Type
Range
1° F
1°C
Input
Type
Range
1° F
1°C

Type J or L*
Iron-Constantan

-100 to +1600
-73 to +871
Type R
PT 13%-PT

0 to 3200
-17 to +1760
Type N*
Ni Chr Si-Ni Si

-100 to +2372
-73 to +1300

Type K*
Chromel-Alumel

-200 to +2500
-129 to +1371
Type S
PT 10%-PT

0 to 3200
-17 to +1760

Type T*
Copper-Constantan

-350 to +750
-212 to +398
Type B
PT 6% RE-PT 30% RE

+75 to 3308
+24 to 1820

Type E*
Chromel-Constantan

-100 to +1800
-73 to +982
Type C
W 5% RE-W 26% RE

0 to 4208
-17 to 2320

* These Input Types can be set for 0.1°

display. If temperature goes above 999.9° or
less than -199.9° the display will return the
whole degree resolution.

RTD Types

Input
Type

Range
1° F
1°C

100 Ohm Platinum
0.00385 DIN
Curve*

-328 to +1607
-200 to +875

100 Ohm
Platinum 0.00392
Nist Curve*

-328 to +1607
-200 to +875

120 Ohm Nickel
0.00628 US Ind.
Curve*

-112 to +608
-80 to +320

1000 Ohm
Platinum 0.00385
Nist Curve*

-328 to +1607
-200 to +875

Process Input Types
The 0 to 20 mAdc, 4 to 20 mAdc, 0 to 10 Vdc, 2 to 10 Vdc, and -10 to +10 mVdc inputs are fully scal-
able from a minimum of 100 counts span placed anywhere within the range of -1999 to +9999. Decimal
point position is adjustable from zero places (9999), tenths (999.9), hundredth (99.99), or thousands
(9.999).