If your computer system will be making frequent changes to the control we strongly recommend that
you select the ‘write to RAM’ parameters (Stor = no). If you are primarily reading from the control, there
is no need to change the setting.
Any instruments equipped with any Serial Communications are limited to one
million WRITE cycles to the EEPROM through the Serial Communications Port.
Exceeding this limit will generate a FAIL TEST error. There is no limit to the num-
ber of times you can READ from this instrument EEPROM.
Make sure that the software you use does not write too often to the instrument.
If you have any questions regarding how your software works with the instrument(s), contact your
System Administrator, Programmer, or Software Supplier.
MENU SELECTIONS
PRIMARY MENU
Press INDEX to advance to the next menu item. Press UP ARROW or DOWN ARROW to change the
value in the display. Press ENTER to retain the value.
If StAt (Secondary Menu ) is On, the three program status menu items will appear.
ti
Time remaining for current segment.
##ti
Total run time for segment ##.
##SP
Target Set Point for segment ##.
If StAt (Secondary Menu ) is OFF, the Primary menu operates as follows:
SP1
Set Point 1 Adjust, Control Point 1.
SP2
Set Point 2 Adjust (if equipped), Control Point 2.
Auto
Auto/Manual Station, Select On or OFF.
On
Output operation is automatic (normal operation).
OFF
Output is controlled manually.
See Page 13 for operation of Auto/Manual Station Feature.
If Prog is OFF in the Secondary Menu, Prog (below) will not appear.
Prog
Ramp/Soak Programmer Run/Hols function, Select run or HoLd.
run
Ramp/Soak Programmer is in operation.
HoLd