Dwyer 32A User Manual
Page 26

Page 26
OSUP
Zero Suppression: Select On or OFF. Only with Current and Voltage input types.
OFF
The input range will start at 0 (zero) Input.
On
The input range will start at 4.00 mA or 1.00 V.
Unit
F, C or None.
F
°F descriptor is On and temperature inputs will be displayed in actual degrees
Fahrenheit.
C
°C descriptor is On and temperature inputs will be displayed in actual degrees
Celsius.
nonE
°F and °C descriptors will be Off. This is only available with Current and Voltage
Inputs.
dPt
Decimal Point Positioning: Select 0, 0.0, 0.00, or 0.000. On temperature
type inputs this will only effect the Process Value, SP1, SP2, ALLo, ALHi,
and InPC. For Current and Voltage Inputs all Menu Items related to the Input
will be affected.
0
No decimal Point is selected. This is available for all Input Types.
0.0
One decimal place is available for Type J, K, E, T, L, RTD’s, Current and Voltage
Inputs.
0.00
Two decimal places is only available for Current and Voltage Inputs.
0.000
Three decimal places is only available for Current and Voltage Inputs.
InPt
Input Fault Timer: Select OFF, 0.1 to 540.0 minutes. Whenever an Input is out of range (UFL
or OFL displayed), shorted, or open the timer will start. When the time has elapsed, the
controller will revert to the output condition selected by InPb below. If OFF is selected, the
Input Fault Timer will not be recognized (time =infinite).
InPb
Input Fail Action: Select FAIL, AVE, or PrE. When the Input is out of range (UFL or OFL
displayed) and the Input timer (InPt) time has elapsed, the controller will revert to the
selected condition.
FAIL
Outputs are disabled (go to 0% output).
AVE
The outputs will hold at the last known average percentage of output.
PrE
The outputs will maintain a preprogrammed percentage of output as specified in
PrE1 and PrE2.
PrE1
Preset output for Set Point 1. Select 0 to 100%.
PrE2
Preset output for Set Point 2. Select 0 to 100%.
APCt
Manual and PctO display adjustment. Select rEAL or AdJ.
rEAL
Manual display will display output 0 to 100% relative to actual range of the output.
AdJ
Manual display will display output 0 to 100% relative to the S#OL and S#OH
settings.