Time Proportioning Cycle Time. Select 1tP to 80tP.
1tP A setting of 1tP is recommended for solid state outputs (SSR or 15VDC).
2tP to 80tP Time Proportioning Control is adjustable in 1 second steps.

Recommended for mechanical outputs (relays, solenoids, etc.).
For best contact life, a time should be selected as long as possible
without causing the process to wander.
#PuL Pulsed Time Proportioning Output: Select 1PuL to
7PuL. 1PuL = Linear and 7PuL = most nonlinear. Changes output
linearity for use in cooling applications or for an extremely fast
response processes. At the center of the proportional band, a pulse
value of 1 provides an output of one second on and one second off
(50% output). A pulse value of 2 provides an output of one second
on and two seconds off (33% output). Output at center of band
equals one second on, 2

(pulse value-1)

seconds off.

ProP

For Current (Code 5) outputs only.

The following menu items apply only if your control is equipped with a second set point (last
digit of model number is not zero and Alarm Programming code is zero). If your control does
not have a second set point or if the second output is programmed as Alarm, jump to the"tunE"
menu on the following pages.

Out2

Output selection: Select OnOf, 2tP, 2PuL, or ProP.
ONOF

A setting of ONOF allows the control to operate as a simple on/off mode. This

setting forces the control to turn off at set point, and on at the set point plus the dif
ferential (SP2d). When selected, the Out2/OnOF menu item is followed by
####/SP2d, and the Pb2 selection in the Secondary menu and the S2OL and
S2OH selections in the Secure menu are suppressed.

SP2d Set Point On-Off Differential (hysteresis). Select 1 to 9999
(direct acting), or -1 to -9999 (reverse acting). This value will be neg
ative for reverse acting set points, and positive for direct acting
outputs. Set the value for the amount of difference between the turn
off point set point) and the turn on point. The drawing on the
previous page (See SP1d) shows output behavior for reverse and
direct acting.

##tP

Time Proportioning Cycle Time. Select 1tP to 80tP.
1tP A setting of 1tP is recommended for solid state outputs (SSR or 15VDC).
2tP to 80tP Time Proportioning Control is adjustable in 1 second steps.

Recommended for mechanical outputs (relays, solenoids, etc.).
For best contact life, a time should be selected as long as possible
without causing the process to wander.
#PuL Pulsed Time Proportioning Output: Select 1PuL to
7PuL. 1PuL = Linear and 7PuL = most nonlinear. Changes output
linearity for use in cooling applications or for an extremely fast
response processes. At the center of the proportional band, a pulse
value of 1 provides an output of one second on and one second off
(50% output). A pulse value of 2 provides an output of one second
on and two seconds off (33% output). Output at center of band
equals one second on, 2

(pulse value-1)

seconds off.