beautypg.com

Dwyer 32A User Manual

Page 28

background image

Page 28

If Out1 is set for ##tP, #PUL, or ProP, then S1OL and S1OH (following) appear. If Out1 is set for
ONOF, then skip to S1rE.

S1OL

Set Point Output Low Limit: Select 0 to 100% but not greater than S1OH. This item limits the
lowest output value. This is useful for adding a bias to the process when needed. Factory
set to 0 for output codes 1,2, and 3. Factory set to 20 for output code 5 (20% output equals
4 mA output).

S1OH

Set Point 1 Output High Limit: Select 0 to 100% but not less than S1OL for output codes 1,
2, or 3. Select 0 to 102% but not less than S1OL for output code 5. This item allows setting
the maximum output limit. This is useful with processes that are overpowered. Adjustment to
102% allows setting current output to force a full on condition for output devices which do
not have bias adjustments. Factory set to 100 for all output codes.

If Out1 is set for ##tP, #PUL, or ProP, then skip to S1LP on next page.

S1rE

Set Point 1 Reset. Select OnOF or Hold.
OnOF

Control will automatically reset when process passes back through SP1d.

HoLd

Manual Reset. Reset (acknowledge) by simultaneously pressing the INDEX &
DOWN ARROW
keys for 5 seconds.

S1Pi

Set Point 1 Power Interrupt. Select On or OFF.
On

Alarm Power Interrupt is On. Control will automatically reset on power-up if no
alarm condition exists.

OFF

Alarm Power Interrupt is OFF. Control will power-up in alarm condition regardless
of condition of process.

S1iH

Set Point 1 Inhibit: Select On or OFF.
On

Alarm Inhibit is On. Alarm action is suspended until the process value first enters
a non-alarm condition.

OFF

Alarm Inhibit is OFF.

S1LP

Set Point Lamp: Select O on or OoFF.
O on

Lamp ON when Output is ON.

OoFF

Lamp OFF when Output is ON.