beautypg.com

Dwyer 32A User Manual

Page 16

background image

Page 16

FACTORY DEFAULT PROCEDURE

If for any reason you wish to restore the factory settings or change the function of the second output
between ALarm or Control follow the following procedure.

1.

Turn off power to control

2.

Turn on power to control

3.

While control is performing SELF tESt, press and hold the INDEX and ENTER keys.

4.

The control will display the ROM ID code. Press INDEX.

5.

The control will display FACt dFLt. If you wish to just restore factory settings,
Press ENTER and DOWN ARROW at the same time. The control will be reset to the original
factory settings.

6.

If you wish to change the operation of the second output, press INDEX.

7.

Press INDEX to display SP2. Select Cont or AL.

Cont

Uses SP2 menu items for second output.

AL

Uses ALarm menu items for second output.

8.

Press INDEX to display OPt. If your control is equipped with an option, press the UP ARROW to
display the option number. If the number is flashing, press ENTER. An enabled option does not
flash.

9.

Press INDEX to display ACPt. Select YES or no.

YES

Changes are accepted and control re-boots.

no

Changes are discarded and control re-boots.