Address Content
Explanation
1026H
Upper-limit alarm 2
Please refer to the contents of the “Alarm Outputs” for detail
1027H
Lower-limit alarm 2
Please refer to the contents of the “Alarm Outputs” for detail
1028H
Upper-limit alarm 3
Please refer to the contents of the “Alarm Outputs” for detail
1029H
Lower-limit alarm 3
Please refer to the contents of the “Alarm Outputs” for detail
102AH
Read LED status
b0 : Alm3, b1: Alm2, b2: F, b3: _, b4: Alm1, b5: OUT2, b6:
OUT1, b7: AT
102BH
Read push button status
b0 : Set, b1 : Select, b2 : Up, b3 : Down. 0 is to push
102CH
Setting lock status
0 : Normal, 1 : All setting lock, 11 : Lock others than SV value
102FH
Software version
V1.00 indicates 0x100
1030H
Start pattern number
0 ~ 7
1040H~
Actual step number setting inside the
0 ~ 7 = N, indicate that this pattern is executed from step 0 to
1047H
correspond pattern step N
1050H~
Cycle number for repeating the execution of 0 ~ 99 indicate that this pattern has been executed for 1~100
1057H
the correspond pattern
times
1060H~
Link pattern number setting of the
0 ~ 8, 8 indicates the program end. 0~7 indicates the next
1067H
correspond pattern
execution pattern number after executing the current pattern
2000H~
Pattern 0~7 temperature set point setting
-999 ~ 9999
203FH
Pattern 0 temperature is set to
2000H~2007H
2080H~
Pattern 0~7 execution time setting
Time 0 ~ 900 (1 minute per scale)
20BFH
Pattern 0 time is set to 2080H~2087H
6.
Address and Content of Bit Register: ( First bit of reading will put into LSB, Write data =
FF00H for bit set, 0000H for bit clear)
Page 25
Address Content
Explanation
0810H
Communication write-in selection
Communication write in disabled: 0 (default), Communication
write in enabled: 1
0811H
Temperature unit display selection
oC / linear input (default) : 1 , oF : 0
0812H
Decimal point position selection
Except for the thermocouple B, S, R type, all the other
thermocouple type are valid. (0 or 1)
0813H
AT setting
OFF: 0 (default), ON : 1
0814H
Control RUN/STOP setting
0 : STOP, 1 : RUN (default)
0815H
STOP setting for PID program control
0: RUN (default), 1: STOP
0816H
Temporarily STOP for PID program control 0: RUN (default), 1: Temporarily STOP