Dwyer 8B User Manual
Page 24
Page 24
Communication Register List
1.
Supporting transmission speed: 2400, 4800, 9600, 19200, 38400 bps.
2.
Non-supported formats: 7, N, 1 or 8, O, 2 or 8, E, 2.
3.
Communication protocol: Modus (ASCII or RTU).
4.
Function code: 03H to read the contents of register (Max. 8 words). 06H to
write 1 (one) word into register. 02H to read the bits data (Max. 16 bits). 05H to write
1 (one) bit into register.
5.
Address and Content of Data Register:
Address Content
Explanation
1000H
Process value (PV)
Measuring unit is 0.1, updated one time in 0.4 second. The
following reading value display indicates error occurs:
8002H : Initial process (Temperature value is not got yet)
8003H : Temperature sensor is not connected
8004H : Temperature sensor input error
8006H : Cannot get temperature value, ADC input error
8007H : Memory read/write error
1001H
Set point (SV)
Unit is 0.1, oC or oF
1002H
Upper-limit of temperature range
The data content should not be higher than the temperature
range
1003H
Lower-limit of temperature range
The data content should not be lower than the temperature
range
1004H
Input temperature sensor type
Please refer to the contents of the “Temperature Sensor Type
and Temperature Range” for detail
1005H
Control method
0: PID, 1: ON/OFF, 2: manual tuning, 3: PID program control
1006H
Heating/Cooling control selection
0: Heating, 1: Cooling, 2: Heating/Cooling, 3: Cooling/Heating
1007H
1st group of Heating/Cooling control cycle
0~99, 0:0.5 sec
1008H
2nd group of Heating/Cooling control cycle
0~99, 0:0.5 sec
1009H
PB Proportional band
0.1 ~ 999.9
100AH
Ti Integral time
0~9999
100BH
Td Derivative time
0~9999
100CH
Integration default 0~100%, unit is 0.1%
100DH
Proportional control offset error value,
0~100%, unit is 0.1%
when Ti = 0
100EH
The setting of COEF when Dual Loop
0.01 ~ 99.99
output control are used
100FH
The setting of Dead band when Dual Loop
-999 ~ 9999
output control are used
1010H
Hysteresis setting value of the 1st
0 ~ 9999
output group
1011H
Hysteresis setting value of the 2nd
0 ~ 9999
output group
1012H
Output value read and write of Output 1
Unit is 0.1%, write operation is valid under manual tuning
mode only.
1013H
Output value read and write of Output 2
Unit is 0.1%, write operation is valid under manual tuning
mode only.
1014H
Upper-limit regulation of analog linear output 1 Unit = 2.8uA(Current Output)=1.3mV(Linear Voltage Output)
1015H
Lower-limit regulation of analog linear output 1 Unit = 2.8uA(Current Output)=1.3mV(Linear Voltage Output)
1016H
Temperature regulation value
-999~+999, unit: 0.1
1017H
Analog decimal setting
0 ~ 3
101CH
PID parameter selection
0~4
101DH
SV value corresponded to PID value
Only valid within available range, unit: 0.1 scale
1020H
Alarm 1 type
Please refer to the contents of the “Alarm Outputs” for detail
1021H
Alarm 2 type
Please refer to the contents of the “Alarm Outputs” for detail
1022H
Alarm 3 type
Please refer to the contents of the “Alarm Outputs” for detail
1023H
System alarm setting
0 : None (default), 1~3 : Set Alarm 1 to Alarm 3
1024H
Upper-limit alarm 1
Please refer to the contents of the “Alarm Outputs” for detail
1025H
Lower-limit alarm 1
Please refer to the contents of the “Alarm Outputs” for detail