Dwyer 8B User Manual
Page 21
Page 21
Control Mode. Select method of control operation. Can be set
to PID, On-Off, Manual, or Ramp/Soak Programming.
Ramp/Soak Pattern Selection. Allows user to select which of
the 8 ramp/soak patterns to program. Each pattern has 8 steps
which gives a total of 64 possible steps in a single program. When
finished programming all ramp and soak patterns, the parameter
should be set to off. (n = 0 to 7)
Segment Set Point for pattern n and step y. For example the
first step of the first pattern would be SP00. The last step would be
SP77. (n = 0 to 7, y = 0 to 7)
Segment Time for pattern n and step y. For example the first
step of the first pattern would be ti00. The last step would be Ti77.
The value of this parameter will be in HH:MM.
(n = 0 to 7, y = 0 to 7)
Last Step for pattern n. Sets the last step that will be performed in
the current pattern. (n = 0 to 7)
Pattern Loop Setting for pattern n. Sets the number of times
that the current pattern will be repeated. (n = 0 to 7)
Pattern Link for pattern n. Sets the next pattern that will be
performed after the current pattern. When set to off, the
program will end and maintain last set point. (n = to 7)
Heat/Cool Selection. Assigns output 1 and output 2 to be
either heat or cool.
HEAt = Output 1 = Heating
CooL = Output 1 = Cooling
H1C2 = Output 1 = Heating; Output 2 = Cooling
H2C1 = Output 1 = Cooling; Output 2 = Heating
Alarm 1 Setting. Sets operation for Alarm 1. Please see
selection on Alarm Outputs for description of the outputs.
Alarm 2 Setting. Sets operation for Alarm 2. Please see
selection on Alarm Outputs for description of the outputs.
Alarm 3 Setting. Sets operation for Alarm 3. Please see
selection on Alarm Outputs for description of the outputs.
(not available for Dual Loop Output Control)
CtrL
PAtn
SPnY
tinY
PSYn
CYCn
Linn
S-HC
ALA1
ALA2
ALA3