REGULATION MENU
Press the ENTER key while at the Home Display in order to access the Regulation Menu.
Pressing the INDEX key will cycle through the below menu items. The parameter will be
displayed in the top display, while its value will be displayed in the bottom display. The UP
and DOWN arrows change the values of the parameters. The ENTER key must be pressed
after any changes.
Auto Tune. The controller will evaluate the process and select
the PID values to maintain good control. Only available when
the control mode is set to PID.
Start learning the process. After the process has been learned
the menu will revert to oFF.
Disables Auto Tune.
Selection of PID profile. The controller can store up to 4 PID
profiles. The top display will show the PID profile and the
bottom display will show the target set value for that profile.
When Pid4 is selected, the controller will automatically select
which PID profile to use based on the target set values. Only
available when control mode is set to PID. See Programming
and Operation of PID function for more information.
(n = 0 to 4)
Target Set Value associated with each PID Profile.
(n = 0 to 3).
Proportional Band Setting associated with each PID
Profile. (n =0 to 3).
Integral time (reset time) associated with each PID
Profile. (n = 0 to 3).
Derivative time (rate time) associated with each PID
Profile. (n = 0 - 3).
Integral Deviation Offset Correction associated with
each PID Profile. (n = 0 to 4)
AT
on
oFF
Pidn
Svn
Pn
in
dn
ioFn