Supply, Special version of srd960 – Badger Meter SRD/SRI Valve Positioners User Manual
Page 7

FUNCTIONAL SPECIFICATIONS (COMMON DATA FOR SRD960-B OR -C)
Air output ln/h (scfh)
at max. deviation, single and double acting:
Supply air
pressure
bar (psig)
1.4
(20)
3
(45)
6
(90)
without
booster
5)
2 700
(95)
5 000
(177)
7 500
(265)
with
Spool
Valve
4)
6 000
(211)
12 000
(423)
18 000
(636)
with
booster
code F, G
21 000
(742)
with
booster
code H
42 000
(1 484)
Note: The use of boosters in connection with Spool valve
is not recommended.
Travel range
Stroke range . . . . . . . . . . . . 8 ... 260 mm (0.3 ... 10.2 in)
with standard feedback levers; special levers on request
Rotation angle range . . . . . . up to 95 °
(without mechanical stop)
Supply
Supply air pressure
5)
. . . . . . 1.4 ... 6 bar (20 ... 90 psig)
with spool valve
4)
. . . . . . 1.4 ... 7 bar (20 ... 105 psig)
Output to actuator . . . . . . . . 0 to ~100 % of supply air
pressure (up to 5.5 bar at
6 bar supply air pressure)
Air supply
1)
. . . . . . . . . . . . . according to ISO 8573-1
Solid particle size and density class 2
Oil rate . . . . . . . . . . . . . . . . class 3
Pressure dew point 10 K under ambient temperature
For air supply, we recommend the FOXBORO ECKARDT
FRS923 filter regulator.
Response characteristic
2) 3)
Sensitivity . . . . . . . . . . . . . . < 0.1 % of travel span
Non-linearity (terminal
based adjustment) . . . . . . . . < 0.4 % of travel span
Hysteresis . . . . . . . . . . . . . . < 0.3 % of travel span
Supply air dependence. . . . . < 0.1 % / 1 bar (15 psi)
Temperature effect. . . . . . . . < 0.3 % / 10 K
Mechanical vibration
10 to 60 Hz up to 0.14 mm,
60 to 500 Hz up to 2 g . . . . . < 0.25 % of travel span
1)
Pressure dew point 10 K under ambient temperature
2)
Data measured according to VDI/VDE 2177
3)
With stroke 30 mm and lever length 90 mm
4)
Spool valve is the type of amplifier used in device SRD960-C
5)
Standard diaphragm amplifier
Devices SRD960-B and SRD960-Cxxxxxxxxxx-M are using "standard"
diaphragm amplifier
Air consumption (steady state) l
n
/h (scfh)
Supply air
pressure
bar (psig)
1.4
(20)
3
(45)
6
(90)
single
acting
80
(2.8)
130
(4.6)
220
(7.8)
double
acting
130
(4.6)
230
(8.1)
430
(15.2)
Spool
Valve
100
(3.5)
240
(8.5)
500
(17.7)
Special Version of SRD960
SRD960 for actuator with rotation up to 300°
This special version of the SRD960 is designed to be
mounted by means of standard attachment kit (like the
EBZG-R) onto rotary actuator with rotation up to 300°.
This special version is made of a standard SRD960 with
new gears.
To be ordered under special version ECEP EP0265
Please consult TI EVE0109 LP
POS-UM-00012-EN-02
Functional Specifications (Common Data for SRD960-B or -C)
Page 7
August 2014