Badger Meter SRD/SRI Valve Positioners User Manual
Page 13

SRD960 with communication PROFIBUS-PA and FOUNDATION Fieldbus H1
SRD960-xPxxxx or SRD960-xQxxxx
PROFIBUS-PA
Data transfer . . . . . . . . . . . . according to PROFIBUS- PA
profile class B based on EN
50170 and
DIN 19245 part 4
GSD file . . . . . . . . . . . . . . . . the actual file can be down-
loaded from our
homepage
Configuration
Local / Display . . . . . . . . . . . see “Functional Specifications
Software . . . . . . . . . . . . . . . VALcare™ (FDT-Software)
Hardware. . . . . . . . . . . . . . . PC- or PCMCIA-interfaces
from Softing
I/A Series System . . . . . . . . with FBM223
Other control systems . . . . . All Profibus-PA- compatible,
e.g. Siemens SIMATIC PDM
(ProcessDevice Manager)
FOUNDATION Fieldbus H1
Data transfer . . . . . . . . . . . . according to Fieldbus
FOUNDATION Specification
Rev. 1.4, Link-Master (LAS).
Function Blocks . . . . . . . . . . AO, Transducer, Resource,
PID, 2xDI, DO
DD files . . . . . . . . . . . . . . . . the actual file can be down-
loaded from our
homepage
Configuration
Local / Display . . . . . . . . . . . see “Functional Specifications
Software . . . . . . . . . . . . . . . VALcare™ (FDT-Software)
or National Instruments
NI-FBUS configurator
Hardware. . . . . . . . . . . . . . . FBUS-interfaces (AT-FBUS
and PCMCIA- FBUS)
I/A Series System . . . . . . . . with FBM220 / 221
Other control systems . . . . . All Fieldbus FOUNDATION
H1-compatible.
Fisher Rosemount Delta-V,
Honeywell, Yokogawa, ABB
*)
Data of ”Intrinsically Safe” version
For both fieldbus versions
Input signal . . . . . . . . . . . . . digital
Supply voltage . . . . . . . . . . . DC 9 to 32 V *)
max. Supply voltage. . . . . . . DC 48 V
Operating current . . . . . . . . . 10.5 mA ± 0.5
(base current)
Current amplitude . . . . . . . . ± 8 mA
Fault current. . . . . . . . . . . . . base current + 0 mA
(base current + 4 mA by means of independent
FDE-safety circuit) according to IEC 1158-2
Start-up time (init phase) . . . approx. 2 sec
Operating values
Bus connection . . . . . . . . . . Fieldbus interface based
on IEC 1158-2 according to FISCO-Model
(see Electrical certifications)
Power supply . . . . . . . . . . . . Power supply is achieved
dependant on the application by means of fieldbus
power supply units or segment coupler
(common data for SRD960 -B or C)”,
Operation and configuration
(common data for SRD960 -B or C)”,
Operation and configuration
POS-UM-00012-EN-02
Physical Specifications (Common Data for SRD960-B,-C or -T)
Page 13
August 2014