Safety requirements ce label, Safety – Badger Meter SRD/SRI Valve Positioners User Manual
Page 11

1)
Details see Certificates of Conformity. With built-in “Inductive
Limit Switch” Code T only –20 °C
2) Below –20 °C reaction time for value changes is reduced
3) Under service as directed
4) With PROFIBUS or FOUNDATION Fieldbus only, if shield of wiring
is grounded on both sides.
5) With appropriate order only
6) National requirements must be observed
Ambient conditions
Operating conditions . . . . . . acc. to IEC 654-1
The device can be operated at a class Dx location
Ambient temperature for
Operation
1)
. . . . . . . . . . . –40 to 80 °C (–40 to 176 °F)
Transport and storage . . . –40 to 80 °C (–40 to 176 °F)
Storage conditions acc.
to IEC 60721-3-1: . . . . . . 1K5; 1B1; 1C2; 1S3; 1M2
Display
LCD (visible)
2)
. . . . . . . . –25 to 80 °C (–13 to 176 °F)
LEDs . . . . . . . . . . . . . . . –40 to 80 °C (–40 to 176 °F)
Relative humidity . . . . . . . . . up to 100 %
Protection class
acc. to IEC 529. . . . . . . . . IP 66
3)
acc. to NEMA . . . . . . . . . . Type 4X
Electromagnetic compatibility EMC
Operating condititions: . . . . . industrieal environment
Immunity according to
- EN 61 326-1 . . . . . . . . . . . fulfilled
Emission according to
- EN 55 011,
Group 1, Class B . . . . . . . . fulfilled
NAMUR
recommendation NE21. . . . fulfilled
SAFETY REQUIREMENTS
CE label
Electromagnetic
compatibility
4)
. . . . . . . . . . . 2004/108/EG
Low-voltage regulation . . . . . not applicable
Safety
According to EN 61010-1
(or IEC 1010-1) . . . . . . . . . . safety class III
Overvoltage Category I
Internal fuses . . . . . . . . . . . . only with PROFIBUS or
FOUNDATION Fieldbus,
but not replaceable
External fuses . . . . . . . . . . . limitation of power supplies
for fire protection must be observed acc. to
EN 61010-1, appendix F (or IEC 1010-1).
Compliance with the essential health and safety
requirements has been assured by compliance with
EN 50014:1997 + A1 + A2 EN 50018:2000
Electrical Classification
5) 6)
See certificate of conformity EX EVE0109 A (de)(en)
Type of protection ATEX “Ex d – Flameproof”
II 2 G EEx d IIC
Temperature class T4...T6
(Design AD 639)
EC-Type-Examination Certificate
PTB 02 ATEX 1084 X
Permissible ambient temperature range:
Temperature class T4 . . . . . –30 °C to +80 °C
(–22 °F to 176 °F)
Temperature class T4 . . . . . (on request)
–40 °C to +80 °C
(–40 °F to 176 °F)
Temperature class T6 . . . . . –30 °C to +75 °C
(–22 °F to 167 °F)
Temperature class T6 . . . . . (on request)
–40 °C to +75 °C
(–40 °F to 167 °F)
For connections in explosion protected hazardous areas
according to directive 94/9/EG appendix II, with the
following maximum values:
Input circuit:
Maximum electrical power . . . . . . . P max = 2.5 W
Electrical connections . . . . . . . . . . U max = up to 60 V
Self-heating of device surface . . . . 1.3 K/W
Type of protection FM “explosion proof”
Class I Division 1, Groups B, C, D
hazardous locations, indoor and outdoor, NEMA 4X
POS-UM-00012-EN-02
Physical Specifications (Common Data for SRD960-B,-C or -T)
Page 11
August 2014