Badger Meter M-Series M3000 User Manual
Page 27
27
6. The screen returns to DIG OUTPUT 1 33. Press or
activate + twice, then press E.
This is only for Fwd Pulse. (Refer to page 36 - "Digital Out
#1.")
7. Into screen PULSE WIDTH 3E enter a number. Press E.
8. The screen returns to DIG OUTPUT 1 33. Press + three
times, then press E.
SET POINT
This is only for Flow Set Point. (Refer to page 36 - "Digital
Out #1.")
1. Into screen SET PT. MIN 3F enter a number.
NOTE: When the fl ow rate falls below the minimum set point
value (entered as a percentage of full scale,) the output
activates.
2. The Screen returns to DIG OUTPUT 1 33. Press + four
times, then press E.
3. In SET PT. MAX 3G enter a number.
NOTE: When the fl ow rate exceeds the set point max.
value (entered as a percentage of full scale fl ow) the output
activates.
This is only for Flow Set Point. (
Refer to page 36 - "Digital
Out #1.")
OUTPUT TYPE
1. Press or activate the letter E to return to screen DIG
OUTPUT 1 33.
2. In DIG OUTPUT 1 33 press + fi ve times, to Output Type.
3. In OUTPUT TYPE 3H press Normally Open or Normally
Closed.
•
Select N.O. or N.C. for any output. (Refer to page
36, "Digital Output #1.")
• Normally Opened or Closed **Selected** shows
for two seconds.
• The screen goes back to DIG OUTPUT 1 33.
4. Pres + six times, or - once to Select Function.