Measure menu – Badger Meter M-Series M5000 User Manual
Page 23
Measure Menu
Measure
Flow Unit
U
This parameter establishes the unit of measure for the flow rate and full scale flow . Changing this
parameter readjusts the full scale flow parameter . For example, changing from GPM to GPS would
change the full scale flow from 60 gal/min to 1 gal/s .
Display
Flow Unit
Display
Flow Unit
L/s
Liters/Second
gal/s
Gallons/Sec .
L/min
Liters/Minute
gal/min
Gallons/Min .
L/h
Liters/Hour
gal/h
Gallons/Hour
m
3
/s
Cubic Meters/Sec .
MG/d
MillionGallons/Day
m
3
/min
Cubic Meters/Min .
IG/s
ImperialGallons/Sec .
m
3
/h
Cubic Meters/Hour
IG/min
ImperialGallons/Min .
ft
3
/s
Cubic Feet/Sec .
IG/h
ImperialGallons/Hour
ft
3
/m
Cubic Feet/Min .
oz/min
Ounce/Min
ft
3
/h
Cubic Feet/Hour .
bbl/min
Barrel/Min
Totalizer Unit
U
This parameter establishes the units of measure for the totalizers .
Display
Totalizer Unit
L
Liters
hL
Hectoliter
m
3
Cubic Meters
ft
3
Cubic Feet
gal
U .S . Gallons
MG
Million Gallons
IG
Imperial Gallons
bbl
Barrel
oz
Fluid Ounces
ac/ft
Acre per foot
Full Scale Flow
S
This parameter sets the maximum flow that the system is expected to measure . This parameter has
influence on other system parameters, which include:
• Low Flow Cutoff – Changes to full scale flow affect the measuring cut-off threshold of the meter
• Alarm Outputs – Changes to full scale flow adjusts the thresholds for generating setpoint alarms
• Pulse Outputs – Changes to full scale flow adjusts the pulse frequency and duty cycle
Change the full scale flow based on the meter size and the application’s requirements . Verify that the
full scale flow falls within the meter’s suggested flow range limits .
Flow Range: 0 .1…32 .8 ft/s (0 .03…10 m/s)
The full scale flow is valid for both flow directions .
OTEE:
N
If the flow rate exceeds the full scale setting of more than 100%, a FLOW_OVERLOAD_
WARNING message indicates that the configured full scale range has been exceeded . However,
the meter will continue to measure . This will affect the latency of the pulse outputs and
possibly cause overflow .
Using the m5000 main menu programming options
MAG-UM-00219-EN-03