Galvanic isolation, Power supply, Blueport – West Control Solutions SG 45 User Manual
Page 53: Front interface, Bus interface (optional), System interface
GALVANIC ISOLATION
Galvanic isolation between inputs and outputs as well as from
the supply voltage is provided.
Test voltages:
Between power supply and inputs/outputs:
2.3 kV AC, 1 min
Between inputs and outputs:
500 V AC; 1min
Max. permissible voltages:
Between inputs/outputs
against earth:
ß 33 V AC
POWER SUPPLY
Depending on ordered version:
AC supply
Voltage:
90...260 V AC
Frequency:
48...62 Hz
Consumption:
approx. 11.5 VA max.
Universal supply 24 V UC
AC supply:
18...30 V AC
Frequency:
48...62 Hz
DC supply:
18...31 V DC
Consumption:
approx. 8.5 VA / 5.8 W max.
* Instruments with optional system interface:
energization is via the bus connector from field bus coupler or
power supply module
cULus: class 2 only!
Behaviour with power failure
Configuration and parameter settings:Permanent storage in EEPROM
BLUEPORT
®
FRONT INTERFACE
Connection to the controller front via a PC adapter (see ‘Additional
Accessories’). The BlueControl
®
software enables the KS 45 to be
configured, parameters set, and operated.
BUS INTERFACE (OPTIONAL)
RS 485
Connection via bus connector fitted in the top-hat rail. Screened
cables should be used.
Type:
RS 485, copper
Transmission speed:
2,400, 4,800, 9,600, 19,200,
38,400 Bit/sec
Parity:
even, odd, none
Address range:
1...247
Number of controllers per bus
segment:
32
Moreover, repeaters must be used.
Protocol
MODBUS RTU
SYSTEM INTERFACE
For connection to fieldbus couplers
(see system components)
Connection via bus connector fitted in the top-hat rail.
Technical data see data sheet 9498-737-50911.
Technical data
53
UNIFLEX SG 45
safety isolation
functional isolation
Power
relay OUT1
Input INP
di 1 (contact)
Output OUT3
RS 485
System
relay OUT2
Front interface