beautypg.com

Linearization 40, O.act, Lim.1 – West Control Solutions SG 45 User Manual

Page 40: Lim.2, Lim.3, Fai.1, O.typ, Out.0, Out.1, O.src

background image

Outputs Out.1 and Out.2 (relay)

Name

Value range

Description

O.Act

Direction of operation OUT1

0

Direct / normally open

1

Inverse / normally closed

Lim.1

Signal limit 1

0

not active

1

active

Lim.2

Signal limit 2

0

not active

1

active

Lim.3

Signal limit 3

0

not active

1

active

FAi.1

Signal INP fail

0

not active

1

active

Sb.Er

System bus error message

µ (only visible with BlueControl

Ò

!)

0

not active

1

active

Inf.1

Status message for operating hours (only visible with BlueControl

Ò

!)

0

not active

1

active

Inf.2

Status message for number of switching cycles (only visible with BlueControl

Ò

!)

0

not active

1

active

fOut

Forcing of the output (only visible with BlueControl

Ò

!)

0

not active

1

The value for this analog output is defined via interface.

Output Out.3 (analog)

Name

Value range

Description

O.tYP

Signal type OUT3

1

0 ... 20 mA continuous

2

4 ... 20 mA continuous

3

0...10V continuous

4

2...10V continuous

Out.0

-1999

...9999

Skaling of analog output for 0% (0/4mA e.g.. 0/2V )

Out.1

-1999

...9999

Skaling of analog output for 100% (20mA e.g. 10V)

O.Src

Signal source for analog output OUT3

3

Process value (scaled and corrected)

7

Measured value (raw value of bridge signal)

O.FAI

Fail behaviour

0

upscale

1

downscale

fOut

Forcing of the output (only visible with BlueControl

Ò

!)

0

not active

1

the value for this analog input is defined via interface.

Configuration level

SG 45

Configurations

40