Linearization 40, O.act, Lim.1 – West Control Solutions SG 45 User Manual
Page 40: Lim.2, Lim.3, Fai.1, O.typ, Out.0, Out.1, O.src
Outputs Out.1 and Out.2 (relay)
Name
Value range
Description
O.Act
Direction of operation OUT1
0
Direct / normally open
1
Inverse / normally closed
Lim.1
Signal limit 1
0
not active
1
active
Lim.2
Signal limit 2
0
not active
1
active
Lim.3
Signal limit 3
0
not active
1
active
FAi.1
Signal INP fail
0
not active
1
active
Sb.Er
System bus error message
µ (only visible with BlueControl
Ò
!)
0
not active
1
active
Inf.1
Status message for operating hours (only visible with BlueControl
Ò
!)
0
not active
1
active
Inf.2
Status message for number of switching cycles (only visible with BlueControl
Ò
!)
0
not active
1
active
fOut
Forcing of the output (only visible with BlueControl
Ò
!)
0
not active
1
The value for this analog output is defined via interface.
Output Out.3 (analog)
Name
Value range
Description
O.tYP
Signal type OUT3
1
0 ... 20 mA continuous
2
4 ... 20 mA continuous
3
0...10V continuous
4
2...10V continuous
Out.0
-1999
...9999
Skaling of analog output for 0% (0/4mA e.g.. 0/2V )
Out.1
-1999
...9999
Skaling of analog output for 100% (20mA e.g. 10V)
O.Src
Signal source for analog output OUT3
3
Process value (scaled and corrected)
7
Measured value (raw value of bridge signal)
O.FAI
Fail behaviour
0
upscale
1
downscale
fOut
Forcing of the output (only visible with BlueControl
Ò
!)
0
not active
1
the value for this analog input is defined via interface.
Configuration level
SG 45
Configurations
40