6.13
Maintenance manager / error list
In case of one or several errors, the error list is always displayed at the beginning of
the extended operating level .
A current input in the error list (alarm or error) is always indicated by display of letter E .
For display of the error list, press key ô once.
E- display element Description
Possible remedial action
blinks
Alarm due to existing error
- Determine the error type in the error list via the error number
- remove error
on
Error removed, Alarm not ac-
knowledged
- acknowledge alarm in the error list by pressing the È - or
the Ì -key
- the alarm entry is deleted by doing so
off
no error, all alarm entrys deleted
Error list:
Name
Description
Cause
Possible remedial action
E.1
Internal error, cannot be
corrected
E.g. defective EEPROM
Contact PMA service
Return device to manufacturer
E.2
Internal error, resettable
E.g. EMC trouble
Keep measuring and supply cables separate.
Protect contactors by means of RC snubber cir-
cuits
E.3
Configuration error, reset-
table
Missing or faulty configura-
tion
Check interdependencies for configurations and
parameters
E.4
Hardware error
Code number and hardware
not identical
Contact PMA service
FbF.1 INP*) sensor break
Defective sensor
Replace INP sensor
Wiring error
Check INP connection
Overshoot
Change the measuring range
POL.1 INP*) polarity error
Wiring error
Change INP polarity
Lim.1
Lim.2
Lim.3
Latched limit value alarm
1/2/3
Adjusted limit value 1/2/3
exceeded
Check process
Inf.1 Time limit value message
Preset number of operating
hours reached
Application-specific
Inf.2 Switching cycle messa-
ge(digital outputs)
Preset number of switching
cycles reached
Application-specific
*) “
FAIL” is shown on the process value display.