4wir, S.lin, Corr – West Control Solutions CI 45 User Manual
Page 40: In.f, I.fnc, Frq.t

Name
Value range
Description
24
Special 0...450 Ohm
25
Special 0...1600 Ohm
26
Special 0...160 Ohm
30
0...20mA / 4...20 mA
40
0...10V / 2...10 V (Inp.1 only)
41
Special (-2,5...115 mV)
42
Special (-25...1150 mV)
43
Special (-25...90 mV)
44
Special (-500...500 mV)
45
Special (-5...5 V) (Inp.1 only)
46
Special (-10...10 V) (Inp.1 only)
47
Special (-200..200 mV)
50
Potentiometer 0...160 Ohm
51
Potentiometer 0...450 Ohm
52
Potentiometer 0...1600 Ohm
53
Potentiometer 0...4500 Ohm
4wir
Resistance connection type (Inp.1 only)
0
3-wire connection
1
4-wire connection
S.Lin
Linearization only adjustable with
S.tYP:18, 23 ... 47
0
none
1
Special linearization. Producing a linearization table is possible via BlueControl
(Engineering-Tool). Preset is the characteristic for KTY 11-6 temperature sensors.
Corr
Measured value correction / scaling
0
No correction
1
Offset correction (at
CAL -level)
2
2-point correction (at
CAL -level)
3
Scaling (at
PArA -level)
In.F
OFF,
-1999...9999
Substitute value in case of a fault. This value is used for calculations, if there is a
fault at the input (e.g. FAIL).
fAI1
(fAI2)
Forcing of analog input INP1, INP2
µ (only visible with BlueControl!)
0
Not active
1
The value for this analog input is preset via interface
Counter / frequency input
µ
Name
Value range
Description
I.Fnc
Function selection
µ
0
Control input
1
Up counter, positive edge
2
Up counter, negative edge
3
Down counter, positive edge
4
Down counter, negative edge
5
Frequency measurement
Frq.t
0,1 … 20
Frequency gate time [s]
µ
Configuration level
40
Configurations
UNIFLEX CI 45