4 frequency output (optional) 35, 5 analog output forcing 35, Forcing 35 – West Control Solutions CI 45 User Manual

Page 35

background image

6.15.4

Frequency output (optional)

The analog output signal for voltage can be selected also as a frequency output with setting:

ConF / Out.3:

O.tYP

=

6

Out.3 0...10V frequency output

Setting

O.Src defines the signal source of the frequency output value.

Example:

O.Src = 3 signal source for Out.3 is the process value

Output range scaling is done via parameter pairs

Out.L/ FrQ.L and Out.H/ FrQ.H. Values Out.L and

Out.H are specified in physical units, FrQ.L and FrQ.H are specified in Hz.

Example:

20°C

= 5 Hz

200°C = 500 Hz
Settings:

Ou.L = 20;

Frq.L = 5,0

Ou.H = 200;

Frq.H = 500,0

The output behaviour in case of input value error can be defined via

O.FAI .

g

Please, note that the lower the span the higher the effect of input variations and resolution steps

g

Signals exceeding the permissible frequency range cause deviations from the square shape of frequency
waves.

6.15.5

Analog output forcing

By adjusting f.Out = 1 (only via BlueControl), the output can be configured for value input via interface, or by means of
an input value at extended operating level (=Forcing).

g

This setting can be used also for e.g. testing the cables and units connected in the output circuit.

g

This function can also realize a setpoint potentiometer.

Functions

UNIFLEX CI 45

Analog output configuration

35

f [Hz]

(V)

Quelle
source

Frq.H

Frq.L

Out.L

Out.H

phys. Größe
phys. size