West Control Solutions N4400 User Manual
Page 20
![background image](/manuals/370824/20/background.png)
8.3
PARAMETERS WHICH APPLY TO A SPECIFIC PROGRAM AS A
WHOLE
Parameter
Message
Display
Function
Available Settings
(Lower Main Display)
Cycle Count
Defines the number of times a
program will be executed
1 - 9999 Program will execute the
set number of cycles
Program will repeat
indefinitely
Auto Hold
Selects operation of Auto Hold
facility (relative to setpoint) - see
Figure 8-1.
No Auto Hold
Auto Hold above SP only
Auto Hold below SP only
Auto Hold above and
below SP
Hold Band
Defines the width of the Hold
Band - see Figure 8-1
Numerical value - 0 to span
Hold on
Defines whether the Auto Hold
facility is used on Ramps only, on
Dwells only or on both Ramps
and Dwells
Auto Hold on Ramps
and Dwells
Auto Hold on Dwells only
Auto Hold on Ramps
only
Pre-x60
Defines whether the timebase for
the program is pre-selected to be
hours/minutes or
minutes/seconds
No pre-selection
Minutes/seconds
Hours/minutes
Timer
(RTC only)
Selects/de-selects timer control of
program
or
Start Hour
(Timer On)
Defines start time for program
24.00 (0.00) to 23.59
Start Day
(Timer On)
Defines day(s) for program to be
run
Sun, Mon, tuE, WEd, thu, Fri,
SAt, 5 dY (Mon - Fri), 6 dY (Mon
- Sat) or ALL (all seven days of
the week)
This se quence may be viewed/ed ited for any pro gram by sim ply chang ing the Pro gram
Num ber with the PROG key, then step ping through the pa rame ters with the Scroll key.
Page 8-3
59215-8
59215