PARAMETERS COMMON TO ALL PROGRAMS (GLOBAL)
Parameter
Message
Display
Function
Available Settings
(Lower Main Display)
Start On
Setpoint value at start of each
program
Current SP
Current PV
End On
Setpoint value at end of each
program
Final SP
1
Controller SP
Delay Time
Delay (hours/minutes) between
program initiation and program
start
Numerical value (decimal point id
de-limiter between hours and
minutes)
Program Lock
Operator changes permitted to
program definitions whilst a
program is running/held?
Not permitted
Permitted
Power Fail
Recovery
Response to restoration of power
after a power failure
0.000 or 1.000 if no RTC;
0.00 or Time (0.01 - 24.00) if RTC
fitted.
0.00 = Cold Start
2
1.00 or Time = Warm Start
3
RTC Time
4
Real Time Clock initial setting
(hours.minutes)
0.10 - 24.00
RTC Day
4
Real Time Clock initial setting
(day of week)
Sun, Mon, tuE, WEd, thu, Fri or
SAt
External
Selection
Functions which may be
controlled externally
No external
selection
Program
selection only
Run, Hold, Abort,
x60 functions only
All program and run
control selections
Lock Code
5
Lock Code for Program Define
Mode
0 - 9999. Default = 10.
59215-8
Page 8-2
59215
1
The final setpoint value for the End Marker of each program - see Subsection 8.4.
2
Cold Start = Base Mode with Program No. as when power failed and Segment No. blank.
3
Warm Start = resumption from point when power failed (with RTC, if time has not expired,
otherwise Cold Start).
4
Available only if RTC option fitted.
5
Only applicable if Setpoint Programmer is configured to have two lock codes.