Safety Relevant Parameters for the Quasar 900 Open Path Gas Detector
57
C
SIL-2 Features
➣ In this appendix…
Safety Relevant Parameters for the Quasar
900 Open Path Gas Detector
page 57
General Conditions for Safe Use
page 58
This appendix details the special conditions to comply with the requirements
of EN 61508 for SIL-2.
The SafEye Quasar 900 IR Open-Path Gas Detector can be used in low and
high demand mode applications, see IEC 61508-4:2010, Chapter 3.5.16.
C.1
Safety Relevant Parameters for the Quasar
900 Open Path Gas Detector
Type:
B
Structure:
1oo1
HFT:
0
Main time to repair:
72 h
Proof-Test-Interval:
52 weeks
DC = 94%
PFD
avg
= 6.45x 10
-4
PFD
%_SIL2
= 6,4 %
PFH = 1.15 x 10
-7
1/h
PFH
%_SIL2
= 11,5 %
S
2056.1fit
D
1976.1fit
DU
114.8fit
SD
1933.4fit
DD
1861.4fit
SFF
97 %