2 rs-485 interface, 4 system setup, 1 detection function programming – Spectrex Quasar 900 Open-Path Gas Detection System User Manual

Page 28: Rs-485 interface, System setup, Detection function programming

background image

SafEye

TM

Quasar 900 Gas Detector

16

System Setup

Table 5: Standard (default) 0-20mA Current for the Gas Channel

Current Reading

Status and Description

0mA +0.3mA

Fault in 0-20mA loop

1mA ±0.3mA

Zero Calibration (In Progress), Fault 2

2mA ±0.3mA

Fault 1 (non-Critical)

2.5mA ± 0.3mA

Misalignment fault

3mA ±0.3mA

“Maintenance Call”

4mA±0.5mA

No gas present

4-20mA

Continuous measuring of gas concentration at a
range between 0 and full scale. For methane and

propane
This translates to 3.2mA per LEL.m and for ethylene
to 2mA per LEL.m.

21mA

Concentration is over the range limit (more than full-
scale concentration).

3.3.2 RS-485 Interface

The RS-485 input/output sends complete data information to a PC and
receives data or control commands from the PC. The protocol is Modbus
compatible. The communication with the PC that is operated through the
interface is executed only when used with appropriate host software.

3.4

System Setup

This section includes the following topics:

Detection Function Programming, page 16

Detection Setup Function, page 17

Detector Default Setup, page 18

3.4.1 Detection Function Programming

The SafEye Quasar 900 incorporates several functions that can be set by the
customer using:

Host software. Refer to manual TM 888050 for programming
instructions.

Handheld unit (P/N 799810). Refer to manual TM 799060 for
programming instructions. The connection of the handheld to the
detector is fast and intrinsically safe and allows function change with no
need to open the detector.