beautypg.com

8 troubleshooting, Troubleshooting, Table 14: troubleshooting – Spectrex Quasar 900 Open-Path Gas Detection System User Manual

Page 57: 8troubleshooting

background image

Periodic Maintenance

45

8

Troubleshooting

Table 14: Troubleshooting

Problem

Cause

Solution

“Maintenance call”
status or R and S are
below 2V DC at Gain

9

Poor alignment

Perform alignment

Dirt on the
window

Clean the window

Poor light source Replace the light source
Detector fault

Replace/repair Detector

NQRat below the
permitted limit

Gas in the path

Make sure that the path is
clean and the weather

conditions are good

NQRat above the
permitted limit

Poor alignment

Perform alignment

Temperature higher
than 25° C beyond
the room

temperature

Electronic
problem

Replace/repair Detector

Ratio1 and Ratio2 out
of the limit

Poor alignment

Perform alignment

Dirt on the
window

Clean the window

Detector fault

Replace/repair Detector

Voltage less than 16V
DC. The Detector at

“V” fault

Low input
voltage

Check the power supply and
installation