8 troubleshooting, Troubleshooting, Table 14: troubleshooting – Spectrex Quasar 900 Open-Path Gas Detection System User Manual
Page 57: 8troubleshooting
Periodic Maintenance
45
8
Troubleshooting
Table 14: Troubleshooting
Problem
Cause
Solution
“Maintenance call”
status or R and S are
below 2V DC at Gain
9
Poor alignment
Perform alignment
Dirt on the
window
Clean the window
Poor light source Replace the light source
Detector fault
Replace/repair Detector
NQRat below the
permitted limit
Gas in the path
Make sure that the path is
clean and the weather
conditions are good
NQRat above the
permitted limit
Poor alignment
Perform alignment
Temperature higher
than 25° C beyond
the room
temperature
Electronic
problem
Replace/repair Detector
Ratio1 and Ratio2 out
of the limit
Poor alignment
Perform alignment
Dirt on the
window
Clean the window
Detector fault
Replace/repair Detector
Voltage less than 16V
DC. The Detector at
“V” fault
Low input
voltage
Check the power supply and
installation