2 fm / fmc, 3 sil-2, 4 functional test – Spectrex Quasar 900 Open-Path Gas Detection System User Manual
Page 20: 5 models and types, Fm / fmc, Sil-2, Functional test, Models and types, Table 2: model numbers and installation distances
SafEye
TM
Quasar 900 Gas Detector
8
Models and Types
2.4.2 FM / FMC
The Quasar 900 is approved to FM / FMC Explosion Proof per:
Class I, Div. 1 Group B, C and D, T6 -58°F (-50°C) ≤ Ta ≤ 149°F (65°C)
Dust Ignition Proof – Class II/III Div. 1, Group E, F and G.
Ingress Protection – IP66 & IP68, NEMA 250 Type 6P.
IP68 is rated for 2 meter depth for 45 minutes.
2.4.3 SIL-2
The Quasar 900 Is TUV approved for SIL2 requirements per IEC 61508.
The alert condition according to SIL-2 can be implemented by alert signal
via 0-20mA current loop.
For more details and guidelines on configuring, installing, operating and
servicing, see SIL-2 Features, page 57, and TUV report no. 968/EZ
619.00/13.
2.4.4 Functional Test
The Quasar 900 was functional approved per FM 6325
The Quasar 900 was functional tested by FM per EN60079-29-4
2.5
Models and Types
The Quasar 900 includes 4 models with the same detector and different
source. That gives the ability to get detection at distances of 7-200m.
Table 2: Model Numbers and Installation Distances
Model
No.
Detector
Source
Min.
Installation
Distance
Max.
Installation
Distance
901
QR-X-11X
QT-X-11X
23 ft (7 m)
66 ft. (20 m)
902
QR-X-11X
QT-X-21X
50 ft (15 m)
132 ft. (40 m)
903
QR-X-11X
QT-X-31X
115 ft (35 m) 330 ft. (100m)
904
QR-X-11X
QT-X-41X
265 ft (80 m) 660 ft. (200 m)