34

Detector Terminal Wiring

5.8

Detector Terminal Wiring

The Detector has six wiring terminals.

The following describes the function of each electrical terminal of the
detectors.

Table 11: Wiring Options

Terminal

No.

Function

1

Power +24V DC

2

Return +24V DC

3

0-20mA (Input)

4

0-20mA (Output)

5

RS-485 (+)

6

RS-485 (-)

5.9

Flash Source Wiring

5.9.1 Wiring

To install the wiring:

1

Release the back screw bolt (item 15, Figure 5), and open the source
back cover (item 14, fig. 4). The chamber is now revealed.

2

Remove the protective plug mounted on the source conduit/cable entry
inlet; pull the wires through the source inlet (item 4, Figure 7). Use a
3/4” – 14NPT or M25x1.5 explosion-proof conduit connection / cable
gland to assemble the cable / explosion-proof conduit to the Detector.

3

Connect the wires to the required terminals (item 2, Figure 7) according
to the wiring diagram. See paragraph Terminal Wiring, page 35 and
Figure 11 Appendix A.

4

Connect the grounding wire to the ground screw outside Detector
(item 3, Figure 7). The source must be well grounded to Earth Ground.

5

Place and secure the source back cover by screwing the cover and
secure the back screw bolt.