beautypg.com

4 technical specifications, 1 general specifications, Technical specifications – Spectrex Quasar 900 Open-Path Gas Detection System User Manual

Page 31: General specifications, Table 8: detection distance range, 4technical specifications

background image

General Specifications

19

4

Technical Specifications

In this chapter…

General Specifications

page 19

Electrical Specifications

page 20

Mechanical Specifications

page 21

Environmental Specifications

page 22

4.1

General Specifications

Detected Gases:

Simultaneous detection of C1-C8
flammable gases

Detection Distance range:

Table 8

Table 8: Detection Distance Range

Model

No.

Detector

Source

Min.

Installation

Distance

Max.

Installation

Distance

901

QR-X-11X

QT-X-11X

23 ft (7 m)

66 ft (20 m)

902

QR-X-11X

QT-X-21X

50 ft (15 m)

132 ft (40 m)

903

QR-X-11X

QT-X-31X

115 ft (35 m)

330 ft (100m)

904

QR-X-11X

QT-X-41X

265 ft (80 m)

660 ft (200m)

Response Time:

3 sec to T90

Spectral Response:

2.0 - 3.0 micron

Sensitivity Range:

Full
Scale

LEL.m.

Warning
LEL.m.

Alarm
LEL.m.

Gas 1 Methane 5

1

3

Gas 2 Propane

5

1

3

Gas 3 Ethylene 8

1.6

4.8

Field of View:

Line of Sight

Alignment
Tolerance:

± 0.5°

Drift:

± 7.5% of the reading or ±4% of the full scale
(whichever is greater)

Minimum Detectable

Level:

0.15 LEL.m

Temperature Range: -67°F (-55°C) to +149°F (+65°C)