General Specifications
19
4
Technical Specifications
➣ In this chapter…
page 19
page 20
page 21
page 22
4.1
General Specifications
Detected Gases:
Simultaneous detection of C1-C8
flammable gases
Detection Distance range:
Table 8: Detection Distance Range
Model
No.
Detector
Source
Min.
Installation
Distance
Max.
Installation
Distance
901
QR-X-11X
QT-X-11X
23 ft (7 m)
66 ft (20 m)
902
QR-X-11X
QT-X-21X
50 ft (15 m)
132 ft (40 m)
903
QR-X-11X
QT-X-31X
115 ft (35 m)
330 ft (100m)
904
QR-X-11X
QT-X-41X
265 ft (80 m)
660 ft (200m)
Response Time:
3 sec to T90
Spectral Response:
2.0 - 3.0 micron
Sensitivity Range:
Full
Scale
LEL.m.
Warning
LEL.m.
Alarm
LEL.m.
Gas 1 Methane 5
1
3
Gas 2 Propane
5
1
3
Gas 3 Ethylene 8
1.6
4.8
Field of View:
Line of Sight
Alignment
Tolerance:
± 0.5°
Drift:
± 7.5% of the reading or ±4% of the full scale
(whichever is greater)
Minimum Detectable
Level:
0.15 LEL.m
Temperature Range: -67°F (-55°C) to +149°F (+65°C)