3.4.2 Detection Setup Function

See Detector Default Setup, page 18 for default settings.

Setup includes the following options:

Gas Calibration, page 17

Zero Calibration, page 17

Address Setup, page 17

Heated Optic Operation, page 17

3.4.2.1 Gas Calibration

Three gas types can be selected for maximum compatibility to the required
measured gas(es).

Gas Types:

Methane – full scale 5 LEL.m.

Propane – full scale 5 LEL.m.

Ethylene – full scale 8 LEL.m.

These three calibrations are standard calibrations.

3.4.2.2 Zero Calibration

Enable – Zero calibration is performed according to background

Disable – The Detectors are not updated due to change of background

3.4.2.3 Address Setup

The Detector provides up to 247 addresses that can be used in RS-485
communication link.

3.4.2.4 Heated Optic Operation

The heated optics for the Detector unit can be defined as one of the
following modes:

OFF -Not operated

ON -Operated continuously

AUTO - On, per temperature change (default)

When operated per temperature change, the user can define the start
temperature below which the window will be heated between 0 to 50°C. The
Detector will stop heating the window when the temperature will be 15°C
above the defined temperature.

This feature relates to the Detector only.

The Source heated optic must be defined with the order in two options:

Heated continuously.

Start heating below 41°F (5°C). (default)