beautypg.com

2 approvals, 3 mechanical specifications, 4 environmental specifications – Spectrex 20/20MPI - Commercial IR3 Flame Detector User Manual

Page 34: Approvals, Mechanical specifications, Environmental specifications

background image

SharpEye

TM

IR3 Flame Detector User Guide

22

User and Maintenance Manual

Communication Network:

The detector is equipped with an RS-485 communication link that can be
used in installations with computerized controllers. The communications
protocol is Modbus compatible.

This protocol is a standard and widely used.

It enables continuous communication between a single standard
Modbus controller (Master device) and a serial Network of up to 247
detectors.

It enables connection between different types of Spectrex detectors
or other Modbus devices to the same Network.

5.2

Approvals

Functional Approvals
• EN54-10 pending per VdS
• FM approved per FM3260

5.3

Mechanical Specifications

Enclosure: Polycarbonate

Functional Test: FM functional test per FM3260

Water and dust tight: IP55 per EN 60529

Electronic Modules: Conformal coated.

Electrical connection: M20 Gland Connection

Dimensions: 4.7” diameter x 2.9” (119 mm x 74 mm)

Weight:

Detector: 10.6 oz. (300g)

Tilt Mount: 2.5 oz. (70g)

5.4

Environmental Specifications

Electromagnetic Compatibility (EMC)

This product is in conformance with EMC directive 89/336/EC.

Radiated Emission

EN61000-6-3

Conducted Emission EN61000-6-3

Radiated Immunity EN50130-4

Conducted Immunity EN50130-4

ESD EN50130-4

Burst EN50130-4

Surge EN50130-4