3 false alarms prevention, False alarms prevention, Table 3: immunity to false alarm sources – Spectrex 20/20MPI - Commercial IR3 Flame Detector User Manual
Page 22
SharpEye
TM
IR3 Flame Detector User Guide
10
False Alarms Prevention
3.3
False Alarms Prevention
The detector does not provide an alarm or a warning signal as a reaction to
the radiation sources specified in Table 3.
Table 3: Immunity to False Alarm Sources
Radiation Source
Immunity Distance
ft.(m)
Sunlight
IAD
Indirect or reflected sunlight
IAD
Incandescent frosted glass light, 100 W
IAD
Incandescent clear glass light, rough service, 100 W
IAD
Fluorescent light with white enamel reflector,
standard office or shop, 40 W (or two 20 W)
IAD
Electric arc [12mm (15/32 in) gap at 4000 V
alternating current, 60 Hz]
IAD
Arc welding [4 mm (5/32 in) rod; 240 A]
See Table 4
Ambient light extremes (darkness to bright light
with snow, water, rain, desert glare and fog)
IAD
Bright colored clothing, including red and safety
orange.
IAD
Electronic flash (180 watt-seconds minimum
output)
IAD
Movie light, 625 W quartz DWY lamp (Sylvania
S.G.-55 or equivalent)
6.5 (2)
Flashlight (MX 991/U)
IAD
Radiation heater, 1500 W
IAD
Radiation heater, 1000 W with fan
IAD
Quartz lamp (1000 W)
10 (3)
Mercury vapor lamp
IAD
Grinding metal
IAD
Lit cigar
1 (0.3)
Lit cigarette
1 (0.3)
Match, wood, stick including flare up
10 (3)
Grinding metal
IAD
Notes:
IAD = Immune at Any Distance.
All sources are chopped from 0 to 20Hz.