beautypg.com

3 false alarms prevention, False alarms prevention, Table 3: immunity to false alarm sources – Spectrex 20/20MPI - Commercial IR3 Flame Detector User Manual

Page 22

background image

SharpEye

TM

IR3 Flame Detector User Guide

10

False Alarms Prevention

3.3

False Alarms Prevention

The detector does not provide an alarm or a warning signal as a reaction to
the radiation sources specified in Table 3.

Table 3: Immunity to False Alarm Sources

Radiation Source

Immunity Distance
ft.(m)

Sunlight

IAD

Indirect or reflected sunlight

IAD

Incandescent frosted glass light, 100 W

IAD

Incandescent clear glass light, rough service, 100 W

IAD

Fluorescent light with white enamel reflector,

standard office or shop, 40 W (or two 20 W)

IAD

Electric arc [12mm (15/32 in) gap at 4000 V
alternating current, 60 Hz]

IAD

Arc welding [4 mm (5/32 in) rod; 240 A]

See Table 4

Ambient light extremes (darkness to bright light
with snow, water, rain, desert glare and fog)

IAD

Bright colored clothing, including red and safety
orange.

IAD

Electronic flash (180 watt-seconds minimum

output)

IAD

Movie light, 625 W quartz DWY lamp (Sylvania
S.G.-55 or equivalent)

6.5 (2)

Flashlight (MX 991/U)

IAD

Radiation heater, 1500 W

IAD

Radiation heater, 1000 W with fan

IAD

Quartz lamp (1000 W)

10 (3)

Mercury vapor lamp

IAD

Grinding metal

IAD

Lit cigar

1 (0.3)

Lit cigarette

1 (0.3)

Match, wood, stick including flare up

10 (3)

Grinding metal

IAD

Notes:

IAD = Immune at Any Distance.

All sources are chopped from 0 to 20Hz.