1 optional latching, 2 built-in-test, Optional latching – Spectrex 20/20MPI - Commercial IR3 Flame Detector User Manual
Page 27: Built-in-test, Table 7: detector state with output signals
TM 20/20MPI, Rev (D) September 2013
Output Signals
15
Table 7: Detector State with Output Signals
Detector State
Color
LED
Flashing
LED
Alarm
Relay
1
Fault
Relay
1
0-20 mA
Output
2
Normal
Green
1 Hz
Off
On
4 mA
Warning
Red
2 Hz
Off
On
16 mA
Alarm
3
Red
Steady
On
On
20 mA
Latch
4
Red
Steady
On
On
20 mA
BIT Fault
5
Yellow
4 Hz
Off
Off
2 mA
Warning at BIT
Fault
Red
2 Hz
Off
Off
16 mA
Alarm at BIT Fault Red
Steady
On
Off
20 mA
Fault
Yellow
4 Hz
Off
Off
0 mA
Notes:
1
Alarm and Fault Relay refer to model 20/20MPI-R.
2
0-20 mA Output refers to model 20/20MPI-M.
3
The alarm outputs are activated as long as the alarm conditions are
present
4
The alarm state can be latched (optional) according to a programmable
function
5
The detector is in its BIT FAULT state until it has passed a successful
BIT, and stops approximately 3 seconds after the fire is no longer
detected.
4.2.1 Optional Latching
The detector has an optional latched alarm output capability, which operates
according to the programmable function. If selected, upon detection of a
fire, the detection signal is latched until manually reset (disconnecting the
power supply). Latching affects the ALARM RELAY, 0-20 mA output, and the
ALARM LED.
4.2.2 Built-In-Test
When the programmable function Alarm BIT at YES is successful, the
0-20 mA output provides 20 mA for 3 sec.