1 optional latching, 2 built-in-test, Optional latching – Spectrex 20/20MPI - Commercial IR3 Flame Detector User Manual

Page 27: Built-in-test, Table 7: detector state with output signals

background image

TM 20/20MPI, Rev (D) September 2013

Output Signals

15

Table 7: Detector State with Output Signals

Detector State

Color
LED

Flashing
LED

Alarm
Relay

1

Fault
Relay

1

0-20 mA
Output

2

Normal

Green

1 Hz

Off

On

4 mA

Warning

Red

2 Hz

Off

On

16 mA

Alarm

3

Red

Steady

On

On

20 mA

Latch

4

Red

Steady

On

On

20 mA

BIT Fault

5

Yellow

4 Hz

Off

Off

2 mA

Warning at BIT

Fault

Red

2 Hz

Off

Off

16 mA

Alarm at BIT Fault Red

Steady

On

Off

20 mA

Fault

Yellow

4 Hz

Off

Off

0 mA

Notes:

1

Alarm and Fault Relay refer to model 20/20MPI-R.

2

0-20 mA Output refers to model 20/20MPI-M.

3

The alarm outputs are activated as long as the alarm conditions are
present

4

The alarm state can be latched (optional) according to a programmable
function

5

The detector is in its BIT FAULT state until it has passed a successful
BIT, and stops approximately 3 seconds after the fire is no longer
detected.

4.2.1 Optional Latching

The detector has an optional latched alarm output capability, which operates
according to the programmable function. If selected, upon detection of a
fire, the detection signal is latched until manually reset (disconnecting the
power supply). Latching affects the ALARM RELAY, 0-20 mA output, and the
ALARM LED.

4.2.2 Built-In-Test

When the programmable function Alarm BIT at YES is successful, the
0-20 mA output provides 20 mA for 3 sec.