Detection Sensitivity

7

3

Performance

In this chapter…

Detection Sensitivity

page 7

Cone of Vision

page 9

False Alarms Prevention

page 10

3.1

Detection Sensitivity

Detection sensitivity is the maximum distance at which the detector will
reliably detect a specific size of fire and typical type of fuel (standard fire).

3.1.1 Standard Fire:

A standard fire is defined as a 1 ft

2

(0.1m

2

) gasoline pan fire with maximum

wind speed of 6.5 ft./sec (2m/sec).

3.1.2 Sensitivity Ranges:

The detector has four user selectable sensitivity ranges. For each range
there are two response levels.

WARNING (Pre-alarm)

ALARM

The detection distance, for the WARNING level, is approximately 10% higher
than the ALARM distance. Alarm response times for a standard fire at a
specified range are shown in Table 1.

Table 1: Alarm Response Time versus Range

10

20

30

40

Sensitivity Range – ft. (m) 33 (10)

65 (20)

100 (30) 140 (43)

Response Time (sec)

5

8

10

10

For some typical ambient conditions the Zeta parameter, as defined in
NFPA 72 for the detector, is 0.005 (1/meter).

Note: Zeta parameters may vary significantly with changes in temperature,
air pressure, humidity, visibility conditions, etc.