3 other fuels, Other fuels, Table 2: response sensitivity ranges – Spectrex 20/20MPI - Commercial IR3 Flame Detector User Manual
Page 20
SharpEye
TM
IR3 Flame Detector User Guide
8
Detection Sensitivity
3.1.3 Other Fuels
The detector reacts to other types of fires as shown in Table 2:
Table 2: Response Sensitivity Ranges
Type Of Fuel
20/20MPI-R
Type Of Fuel
Gasoline
140 ft. (43m)
100%
N-Heptane
140 ft. (43m)
100%
Alcohol 95%
98 ft. (30m)
70%
JP5
98 ft. (30m)
70%
Kerosene
98 ft. (30m)
70%
Diesel Fuel
98 ft. (30m)
70%
Methane*
39 ft. (12m)
28%
IPA
115 ft. (35m)
80%
Methanol
98 ft. (30m)
70%
LPG*
39 ft. (12m)
28%
Polypropylene
49 ft. (15m)
35%
Paper
49 ft. (15m)
35%
* 0.5m plume fire
Pan Fire Size: 1 ft
2
(0.1m2)
Maximum Wind Speed: 6.5 ft./sec (2 m/sec)
Maximum Response Time: 10 sec