beautypg.com

3 other fuels, Other fuels, Table 2: response sensitivity ranges – Spectrex 20/20MPI - Commercial IR3 Flame Detector User Manual

Page 20

background image

SharpEye

TM

IR3 Flame Detector User Guide

8

Detection Sensitivity

3.1.3 Other Fuels

The detector reacts to other types of fires as shown in Table 2:

Table 2: Response Sensitivity Ranges

Type Of Fuel

20/20MPI-R

Type Of Fuel

Gasoline

140 ft. (43m)

100%

N-Heptane

140 ft. (43m)

100%

Alcohol 95%

98 ft. (30m)

70%

JP5

98 ft. (30m)

70%

Kerosene

98 ft. (30m)

70%

Diesel Fuel

98 ft. (30m)

70%

Methane*

39 ft. (12m)

28%

IPA

115 ft. (35m)

80%

Methanol

98 ft. (30m)

70%

LPG*

39 ft. (12m)

28%

Polypropylene

49 ft. (15m)

35%

Paper

49 ft. (15m)

35%

* 0.5m plume fire

Pan Fire Size: 1 ft

2

(0.1m2)

Maximum Wind Speed: 6.5 ft./sec (2 m/sec)

Maximum Response Time: 10 sec