2 output signals, Output signals, Table 5: 20/20mpi status – Spectrex 20/20MPI - Commercial IR3 Flame Detector User Manual
Page 26: Table 6: 20/20mpi output signals, Table 5
SharpEye
TM
IR3 Flame Detector User Guide
14
User and Maintenance Manual
Table 5: 20/20MPI Status
Detector Status
LED color
LED mode
Fault, BIT Fault
Yellow
4 Hz flashing
Normal
Green
1 Hz flashing
Warning
Red
2 Hz flashing
Alarm
Red
Steady
4.2
Output Signals
The detector controls the following outputs:
Model 20/20MPI-R:
Alarm Relay
Fault Relay
RS485
Model 20/20MPI-M:
0-20 mA Stepped Source Configuration
RS485
The detector can be in one of the following states.
Table 6: 20/20MPI Output Signals
Detector Status Description
Normal
The detector is functioning normally.
BIT
The detector performs a Built-In Test.
Warning
Fire detected – warming alarm (pre-alarm) state
Alarm
Fire detected – fire alarm state
Latched Alarm
(Optional)
The alarm outputs are latched due to the detection of a
fire that has already been extinguished.
BIT Fault
A fault is detected during BIT sequence. The detector
will continue to detect fire if the alarm conditions occur.
Fault
A fault is detected when the power supply is too low or
during a software fault.
In each state, the detector activates different outputs, as specified in Table
7.