beautypg.com

2 technical description, 1 features, 2 principles of operation – Spectrex 20/20MPI - Commercial IR3 Flame Detector User Manual

Page 15: 1 hydrocarbon fire detection, 2 identifying the co2 peak, Technical description, Features, Principles of operation, Hydrocarbon fire detection, Identifying the co2 peak

background image

Features

3

2

Technical Description

In this chapter…

Features

page 3

Principles of Operation

page 3

2.1

Features

The SharpEye Model 20/20MPI Mini Triple IR (IR3) Flame Detector includes
the following features:

Detection Range: up to 140 ft. (43m) for a 1 ft

2

(0.1m

2

) n-heptane

pan fire

Ultra High Immunity to False Alarms (see False Alarms Prevention
on page 10)

Advanced Digital Processing of the Dynamic Characteristics of
Fire
: Flickering, Threshold correlation and Ratio

Three Separate IR Channels: Between 3-5 microns

Field Programmable Sensitivity: four ranges

Two Response Levels: Warning and Detection

Solar Blind

Microprocessor Based: Digital signal processing

Built In Test (BIT): Manual and Automatic

Two Options of Electrical Interface:

20/20MPI-R: Dry contact relays

20/20MPI-M: 0-20 mA output (stepped)

Functional Approvals:

EN54-10 Pending per VdS

FM approved per FM3260

2.2

Principles of Operation

2.2.1 Hydrocarbon Fire Detection

The triple IR flame detector detects all conceivable types of hydrocarbon
fires, i.e. any fire, which emits CO2.

2.2.2 Identifying the CO2 Peak

The hydrocarbon fire is characterized by a typical radiation emission. The
CO2 peak emits intense radiation in the spectral band between 4.2 µ - 4.5 µ
and weaker radiation intensity outside this spectral band.