User and Maintenance ManualUser and Maintenance Manual

21

5

Technical Specifications

In this chapter…

Electrical Specifications

page 21

Output Signals

page 22

Environmental Specifications

page 22

5.1

Electrical Specifications

Operating Voltage: 18-32 VDC

Power Consumption:

Max. 16 mA in Stand-by

Max. 40 mA in Alarm

Electrical outputs

Dry Contact Relays:

Table 11: Contact Ratings

Relay Name

Type

Normal
position

Maximum
Ratings

Alarm

SPST

N.O.

2A at 30 VDC

Fault *

SPST

N.C.

2A at 30 VDC

* The FAULT relay is normally energized and the contact is closed during
normal operation of the detector. The contact is open at Fault condition or
low voltage.

0-20 mA Current Output:

The 0-20 mA is source option only.

The maximum permitted load resistor is 600 ohm.

Table 12: 0-20 Current Output

STATE

Output

FAULT

0 + 0.5 mA

BIT FAULT

2 mA±10%

NORMAL

4 mA±10%

WARNING

16 mA±5%

ALARM

20 mA±5%