5 technical specifications, 1 electrical specifications, Technical specifications – Spectrex 20/20MPI - Commercial IR3 Flame Detector User Manual
Page 33: Electrical specifications, Table 11: contact ratings, Table 12: 0-20 current output, 5technical specifications
User and Maintenance ManualUser and Maintenance Manual
21
5
Technical Specifications
➣ In this chapter…
page 21
page 22
page 22
5.1
Electrical Specifications
Operating Voltage: 18-32 VDC
Power Consumption:
Max. 16 mA in Stand-by
Max. 40 mA in Alarm
Electrical outputs
Dry Contact Relays:
Table 11: Contact Ratings
Relay Name
Type
Normal
position
Maximum
Ratings
Alarm
SPST
N.O.
2A at 30 VDC
Fault *
SPST
N.C.
2A at 30 VDC
* The FAULT relay is normally energized and the contact is closed during
normal operation of the detector. The contact is open at Fault condition or
low voltage.
0-20 mA Current Output:
The 0-20 mA is source option only.
The maximum permitted load resistor is 600 ohm.
Table 12: 0-20 Current Output
STATE
Output
FAULT
0 + 0.5 mA
BIT FAULT
2 mA±10%
NORMAL
4 mA±10%
WARNING
16 mA±5%
ALARM
20 mA±5%