beautypg.com

3 detector mode setup, 1 detector setting, 2 detector functions – Spectrex 20/20MPI - Commercial IR3 Flame Detector User Manual

Page 28: 1 sensitivity ranges, 2 alarm delay, Detector mode setup, Detector setting, Detector functions

background image

SharpEye

TM

IR3 Flame Detector User Guide

16

User and Maintenance Manual

4.3

Detector Mode Setup

4.3.1 Detector Setting

Refer to Detector Default Setup on page 18 for default factory settings.

The detector incorporates several functions that can be set by the customer
using Spectrex Host software, which is supplied for each detector shipment,
(refer to manual TM768050 for programming instructions). The Host
software enables you to change functions as described in Detector on
page 16.

4.3.2 Detector Functions

4.3.2.1 Sensitivity Ranges

The detector offers four (4) sensitivity settings. The settings refer to the
gasoline fire of 1 ft

2

from 33 ft. (10 m) to 140 ft. (43m). Detection distances

for other fuels vary.

4.3.2.2 Alarm Delay

The detector is equipped with an Alarm Delay option, which provides
programmable time delays of 0 to 30 seconds with eight (8) fixed settings:

0 seconds

Anti-flare

3 seconds

5 seconds

10 seconds

15 seconds

20 seconds

30 seconds

When an Alarm (Detection) level condition is encountered, the detector
delays the execution of the Alarm output’s relay by the specified period of
time. The detector then evaluates the condition for 3 seconds. If the Alarm
level is still present, the Alarm outputs are activated. If this condition no
longer exists, the detector returns to its standby state. The Alarm delay
option affects the alarm relay and the 0-20 mA output. The LED indicates
warning level during the delay time only if the fire condition exists.

Anti-Flare

Anti-Flare mode is selected to prevent false alarm in locations where fast
flares may be present. The Time delay for fire alarm in this mode is from 2.5
to 15 seconds (mostly less than 10 seconds).