40/40UB Flame Detector

65

E

SIL-2 Features

In this appendix…

40/40UB Flame Detector

page 65

E.1

40/40UB Flame Detector

This appendix details the special conditions to comply with the requirements
of EN 61508 for SIL 2.

The 40/40UB Flame Detector can only be used in low or high demand mode
applications, see IEC 61508.4, Chapter 3.5.12.

E.1.1 Safety Relevant Parameters

Perform the following functional checks of the detector every 30 days:

HFT: 0

PFD: 2.5 x 10

-5

(≈ 0.2% of SIL-2) if only Alarm Relay is used for

alerting.

PFD: 2.8 x 10

-5

(≈ 0.3% of SIL-2) if 4-20mA interface is used as alarm.

SFF: 97% fulfills the conditions of EN 61508 for SIL2

E.1.2 Guidelines for Configuring, Installing, Operating and

Service

The alert conditions according to SIL 2 can be implemented by an:

Alert signal via 20mA current loop

or

Alert signal via alarm relay and the fault relay

E.1.2.1

Conditions for Safe Operating

1

The flame detector shall consist only of the approved hardware and
software modules.

2

The 24V power supply must fulfill the requirements for PELV / SELV of
EN 60950.

3

The automatic BIT (Built-In-Test) must be activated.

4

The set-up parameters must be verified (as described in
Using the 0-20mA Interface for Alerting on page 65, point 1 and in Using
the Alarm Relay Contact for Alerting
on page 66, point 1) and the
function of the 40/40 Flame Detector (flame detection, function of the
0-20mA interface, relay functions) must be checked completely.